BuildCodes.ca
6.913 articles · 4 subsections

Fire Safety Systems

6.9.1

General

6.9.1.1

Fire Safety Requirements

(1)The fire safety characteristics of heating, ventilating and air-conditioning systems shall comply with Subsection 3.6.5.

(2)Characteristics referred to in Sentence (1) include but are not limited to

  • (a) use of combustible materials in duct systems,
  • (b) flame-spread ratings and smoke-developed ratings of duct and pipe materials and coverings,
  • (c) installation of equipment relative to property lines, and
  • (d) requirements for fire dampers and fire stop flaps.
6.9.1.2

Hazardous Gases, Dusts or Liquids

(1)Except as provided in Subsection 6.3.4., systems serving spaces that contain hazardous gases, dusts or liquids shall be designed, constructed and installed in conformance with the provisions of the Fire Code made under the Fire Protection and Prevention Act, 1997, or in the absence of requirements pertinent to such systems in the Fire Code, to good engineering practice such as that described in the publications of the National Fire Protection Association and in the CCBFC NRCC-CONST-56437E, "National Fire Code of Canada.

(2)When indoor piping for Class I flammable liquids is installed in a trench, the trench shall be

  • (a) provided with positive ventilation to the outdoors, or
  • (b) designed to prevent the accumulation of flammable vapours.
6.9.1.3

Commercial Cooking Equipment

(1)Fire protection systems for commercial cooking equipment referred to in Sentence 6.3.1.6.(1) using vegetable oil or animal fat shall conform to

  • (a) ANSI/CAN/UL/ULC 300, "Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment," or
  • (b) ULC/ORD-C1254.6, "Fire Testing of Restaurant Cooking Area Fire Extinguishing System Units."
6.9.2

Dampers and Ductwork

6.9.2.1

Fire Dampers

(1)Fire dampers shall conform to Article 3.1.8.10.

6.9.2.2

Smoke Detectors

(1)Air handling systems shall incorporate smoke detectors where and as required by Article 3.2.4.12.

6.9.2.3

Exhaust Ducts and Outlets

(1)Where an exhaust duct system is used for smoke removal in a high building, the requirements of Article 3.2.6.6. shall apply.

(2)Where exhaust duct systems from more than one fire compartment are connected to an exhaust duct in a vertical service space, the requirements of Article 3.6.3.4. shall apply.

6.9.2.4

Ducts in Exits

(1)Where ducts penetrate fire separations separating exits from the remainder of the building, they shall be in accordance with Article 3.4.4.4.

(2)Duct penetration of fire separations separating exits from the remainder of the building is permitted if the duct

  • (a) is designed for the purposes of Subsection 3.2.6., or
  • (b) only serves the exit from a dedicated rooftop air make-up unit.
6.9.3

Carbon Monoxide Alarms

6.9.3.1

Application

(1)Article 6.9.3.2. applies to every building that

  • (a) contains a residential occupancy, a care occupancy with individual suites, or a care occupancy containing sleeping rooms not within a suite, and contains a fuel-burning appliance or a storage garage, or
  • (b) contains a residential occupancy and is served by a forced-air fuel-burning appliance not contained within the building.

(2)Articles 6.9.3.3. and 6.9.3.4. apply to every building.

6.9.3.2

Location of Carbon Monoxide Alarms

(1)A carbon monoxide alarm shall be installed in a suite of residential occupancy or care occupancy where

  • (a) a fuel-burning appliance or a flue is installed in the suite,
  • (b) a forced-air fuel-burning appliance provides heated air directly to the suite,
  • (c) a fuel-burning appliance or a flue is located in a room, suite or area that shares a common wall or floor or ceiling assembly with the suite, or
  • (d) a storage garage shares a common wall or floor or ceiling assembly with the suite.

(2)Where a carbon monoxide alarm is required by Sentence (1) to be installed in a suite of residential occupancy or care occupancy, other than a suite that consists of a combined living and sleeping area, a carbon monoxide alarm shall be installed

  • (a) adjacent to each sleeping room in the suite, and
  • (b) on each storey without a sleeping room in the suite.

(3)Where a carbon monoxide alarm is required by Sentence (1) to be installed in a suite of residential occupancy or care occupancy that consists of a combined living and sleeping area, a carbon monoxide alarm shall be installed in the combined living and sleeping area.

(4)In addition to the carbon monoxide alarms required to be installed in a suite of residential occupancy or care occupancy in accordance with Sentence (2), a carbon monoxide alarm shall be installed in each sleeping room within the suite where the sleeping room

  • (a) contains a fuel-burning appliance or a flue, or
  • (b) shares a common wall or floor or ceiling assembly with
  • (i) a room, suite or area that is located outside the suite and contains a fuel-burning appliance or a flue, or
  • (ii) a storage garage.

(5)Carbon monoxide alarms shall be installed in public corridors serving suites of residential occupancy where the corridor is directly heated by a forced-air fuel-burning appliance.

(6)Where carbon monoxide alarms are required by Sentence (5) to be installed in a public corridor, the carbon monoxide alarms shall be installed such that

  • (a) there is at least one carbon monoxide alarm in each portion of a divided corridor, and
  • (b) each carbon monoxide alarm in an undivided portion of a corridor is spaced not more than 25 m apart.
6.9.3.3

Location of Carbon Monoxide Alarms in All Buildings

(1)A carbon monoxide alarm shall be installed in service rooms or other areas of a building where the service room or other area

  • (a) contains a fuel-burning appliance used for building services or laundry drying equipment, and
  • (b) is not located within a suite of residential occupancy.
6.9.3.4

Installation and Conformance to Standards

(1)The carbon monoxide alarms required by Articles 6.9.3.2. and 6.9.3.3. shall

  • (a) except as permitted in Sentence (2), be permanently connected to an electrical circuit and shall have no disconnect switch between the overcurrent device and the carbon monoxide alarm,
  • (b) in case the regular power supply to the carbon monoxide alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the carbon monoxide alarm for a period of not less than 8 h in the standby condition, followed by the operation of the carbon monoxide alarm for an alarm signal for at least 12 h,
  • (c) be wired so that
  • (i) activation of one carbon monoxide alarm within a suite of residential occupancy will activate all carbon monoxide alarms within the suite, and
  • (ii) activation of one carbon monoxide alarm located in a public corridor serving suites of residential occupancy will activate all carbon monoxide alarms within the corridor,
  • (d) be audible within sleeping rooms when the intervening doors are closed, where located adjacent to a sleeping room in a suite of residential occupancy, and
  • (e) conform to
  • (i) CAN/CSA-6.19, "Residential Carbon Monoxide Alarming Devices", or
  • (ii) UL 2034, "Single and Multiple Station Carbon Monoxide Alarms".

(2)Where the building is not supplied with electrical power, carbon monoxide alarms are permitted to be battery operated.

(3)Except as permitted in Sentence (4), the carbon monoxide alarms required by Articles 6.9.4.2. and 6.9.4.3. shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code".

(4)Where the building is not supplied with electrical power, carbon monoxide alarms need not have a visual signalling component.

(5)The luminous intensity for visual signalling components required by Sentence (3) that are installed in sleeping rooms or combined living and sleeping areas shall be a minimum of 175 cd.

(6)The visual signalling component required by Sentence (3) need not

  • (a) be integrated with the carbon monoxide alarm provided it is interconnected to it,
  • (b) be on battery backup, or
  • (c) have synchronized flash rates, when installed in a dwelling unit.

(7)The carbon monoxide alarms required by Articles 6.9.3.2. and 6.9.3.3. shall be installed

  • (a) at the manufacturer's recommended height, or
  • (b) in the absence of specific instructions, on or near the ceiling.
6.9.4

Ash Storage

6.9.4.1

Ash Storage Bins

(1)Every ash storage bin shall be constructed of noncombustible material.

(2)Every opening in an ash storage bin shall be protected by a tight-fitting metal door with metal frame securely fastened to the bin.

6.9.4.2

Fireplaces

(1)Fireplaces shall conform to the requirements of Section 9.22.