Means of Egress
General
(1)Stairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.
(1)In addition to the fire protection requirements provided in Subsection 9.9.4., flame-spread ratings, fire-resistance ratings and fire-protection ratings for means of egress shall conform to Section 9.10.
(1)The occupant load of a floor area or part of a floor area shall be based on
- (a) two persons per sleeping room or sleeping area in a dwelling unit or suite, and
- (b) for occupancies other than as described in Clause (a), the number of persons
- (i) for which the area is designed, or
- (ii) determined from Table 3.1.17.1.
Types and Purpose of Exits
(1)Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:
- (a) an exterior doorway,
- (b) an exterior passageway,
- (c) an exterior ramp,
- (d) an exterior stairway,
- (e) a fire escape,
- (f) a horizontal exit,
- (g) an interior passageway,
- (h) an interior ramp, or
- (i) an interior stairway.
(2)Fire escapes shall only be used as exits on existing buildings and shall be designed and installed in conformance with Subsection 3.4.7.
(2.1)Fire escapes shall not be installed on any new building.
(3)Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.10.
(1)An exit shall be designed for no purpose other than for exiting, except that an exit may also serve as an access to a floor area.
(1)Elevators, slide escapes or windows shall not be considered as part of a required means of egress.
(2)Except for floor areas of mercantile occupancy, casement windows not less than 1 060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of egress to provide access to fire escapes, when fire escapes are permitted.
(1)Except for doors serving a single dwelling unit or a house with a secondary suite including their common spaces, at least one door at every principal entrance to a building providing access from the exterior at ground level shall be designed in accordance with the requirements for exits.
(1)Except for curved stairs, the front edge of stair treads in exits and access to exits shall be at right angles to the direction of exit travel.
(1)Treads and landings of exterior exit stairs that serve a hotel shall be designed to be free from ice and snow accumulation.
Dimensions of Means of Egress
(1)This Subsection applies to every means of egress except
- (a) exits that serve not more than one dwelling unit or a house with a secondary suite including their common spaces, and
- (b) access to exits within dwelling units and within houses with a secondary suite including their common spaces.
(1)Except for doors and corridors, the width of every exit facility shall be not less than 900 mm.
(1)The width of every public corridor, corridor used by the public, and exit corridor shall be not less than 1 100 mm.
(1)Except for stairways, doorways and storage garages, the minimum clear height in exits and access to exits shall be 2.1 m.
(2)The clear height in exits and access to exits in a storage garage shall be not less than 2 m.
Fire Protection of Exits
(1)Except as provided in Articles 9.9.4.4. and 9.9.4.6., this Subsection applies to the fire protection of all exits except exits serving not more than one dwelling unit.
(1)Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area.
(2)Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than 45 min.
(3)A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.
(4)A fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.
(5)The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least 50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.
(1)This Article applies to wired glass in doors, and wired glass or glass block in sidelights, where these are installed in fire separations between exit enclosures and floor areas.
(2)Except as provided in Sentence (3), the combined area of glazing in doors and sidelights shall not exceed 0.8 m².
(3)Where an exit enclosure connects with a floor area through an enclosed vestibule or corridor separated from the floor area by fire separations having not less than a 45 min fire-resistance rating, the glazed areas described in Sentence (1) need not be limited as required in Sentence (2).
(1)Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, or another dwelling unit, ancillary space or common space in a house with a secondary suite, the openings in the exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. when the openings in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair or ramp.
(1)Either openings in exterior walls of an exit or openings in adjacent exterior walls of the building the exit serves shall be protected with wired glass in fixed steel frames or glass block installed in accordance with Articles 9.10.13.5. and 9.10.13.7., where
- (a) the exit enclosure has exterior walls that intersect the exterior walls of the building at an angle of less than 135° measured on the outside of the building, and
- (b) the openings in the exterior walls of the building are within 3 m horizontally and less than 2 m above the openings in the exterior walls of the exit.
(1)This Article applies to
- (a) exit doors serving other than an individual dwelling unit, and
- (b) exit doors serving an individual dwelling unit where there is no second and separate exit from the dwelling unit.
(2)Where an exterior exit door described in Sentence (1) in one fire compartment is within 3 m horizontally of an unprotected opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior angle of less than 135°, the opening shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. or with a rated closure conforming to Table 9.10.13.1. with respect to the rating of the fire separation between the two compartments.
(1)Notwithstanding the requirements of Sentences 9.9.4.2.(1), 9.9.8.2.(1) and Article 9.10.9.5., where a suite of Group D or E occupancy is located partly on the first storey and partly on the second storey or partly on the second storey and partly on the third storey, stairways serving the suite need not be constructed as exit stairs provided
- (a) the building is not greater than 3 storeys in building height,
- (b) the suite is separated from other occupancies by a fire separation having a fire-resistance rating of not less than 45 min,
- (c) the area occupied by the suite is not greater than 100 m² per storey, other than the exit level storey,
- (d) the maximum travel distance from any point in the suite to an exterior exit is not greater than 25 m,
- (e) the floor assemblies have a fire-resistance rating of not less than 45 min or are of noncombustible construction,
- (f) the basement and first storey are separated by a fire separation having a fire-resistance rating of not less than 45 min, and
- (g) a smoke alarm is installed on each floor of the suite, including the basement, in accordance with Subsection 9.10.19.
Obstructions and Hazards in Means of Egress
(1)This Subsection applies to obstructions and hazards in every means of egress except those within a dwelling unit or serving not more than one dwelling unit.
(1)Where a corridor contains an occupancy, the occupancy shall not reduce the unobstructed width of the corridor to less than the required width of the corridor.
(1)Except as permitted in Sentence (2), obstructions located within 1 980 mm of the floor shall not project horizontally more than 100 mm into exit passageways, corridors used by the public or public corridors in a manner that would create a hazard for visually impaired persons travelling adjacent to walls.
(2)The horizontal projection of an obstruction referred to in Sentence (1) is permitted to exceed 100 mm where the obstruction extends to less than 680 mm above the floor.
(1)Except as permitted in Subsection 9.9.6. and Article 9.8.7.6., no fixture, turnstile or construction shall project within the required width of an exit.
(1)No obstructions such as posts or turnstiles shall be placed so as to restrict the width of a required means of egress from a floor area or part of a floor area to less than 750 mm unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.
(2)Except as provided in Sentence (3), no obstructions, such as counter gates, that do not meet the requirements for exit doors, shall be placed in a required means of egress from a floor area or part of a floor area unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.
(3)Obstructions, such as counter gates, that do not satisfy Sentence (2), are permitted to be placed in a required means of egress from a part of a floor area in mercantile occupancies and business and personal services occupancies, provided that the part of the floor area served by the obstructed means of egress is not generally accessible to the public.
(1)No mirror shall be placed in or adjacent to any exit so as to confuse the direction of exit, and no mirror or draperies shall be placed on or over exit doors.
(1)Fuel-fired appliances shall not be installed in an exit or corridor serving as an access to exit.
(1)Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.
(1)Except in houses with a secondary suite, ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.
Doors in a Means of Egress
(1)Except as provided in Sentence (4), swinging doors in their swing shall conform to Sentences (2) and (3)
- (a) at exit doors,
- (b) at doors that open into or are located within a public corridor, and
- (c) at doors that open into or are located within another facility that provides access to exit from a suite.
(2)When fully open, doors described in Sentence (1) shall not decrease the required exit width by more than
- (a) 100 mm in exit corridors, and
- (b) 50 mm for other exit facilities.
(3)The swing of doors described in Sentence (1) shall not reduce the width of the path of travel to less than
- (a) the required exit width in exit corridors and passageways, and
- (b) 750 mm on exit stairs or landings.
(4)Doors serving a single dwelling unit or a house with a secondary suite need not comply with Sentences (2) and (3).
(1)Except as provided in Sentences (2) and (3), the clear opening height of doorways shall be not less than 2 030 mm high at
- (a) exit doors,
- (b) doors that open into or are located within a public corridor, and
- (c) doors that open into or are located within another facility that provides access to exit from a suite.
(2)The clear opening height under door closers and other devices in doorways described in Sentence (1) shall be not less than 1 980 mm.
(3)Doorways serving a single dwelling unit or a house with a secondary suite need not comply with Sentences (1) and (2).
(1)Except as provided in Sentence (4), the clear opening width of doorways shall comply with Sentence (2) at
- (a) exit doors, and
- (b) doors that open into or are located within a public corridor or other facility that provides access to exit from a suite.
(2)Doorways described in Sentence (1) shall be
- (a) not less than 800 mm wide where there is only one door leaf,
- (b) not less than 800 mm wide where multiple-leaf doors are installed with only one active leaf having a latching mechanism described in Article 9.9.6.7., and
- (c) not less than 1 210 mm wide where multiple-leaf doors are installed with two active leaves.
(3)In doorways described in Sentence (1) that have multiple-leaf doors installed,
- (a) no active leaf shall be less than 810 mm wide where only one leaf is active, and
- (b) no single leaf shall be less than 610 mm wide where two leaves are active.
(4)Doorways serving a single dwelling unit or a house with a secondary suite need not comply with Sentence (2).
(1)Except as provided in Sentences (4) and (5), required exit doors and doors in required means of egress, except doors in means of egress within dwelling units, shall swing on the vertical axis.
(2)Except as provided in Sentence (5), breakaway sliding doors, installed as required exit doors or required doors in means of egress, shall be identified as swinging doors by means of a label or decal affixed to the door.
(3)Revolving doors shall comply with Article 3.4.6.15.
(4)Movable partitions used to separate a public corridor from an adjacent business and personal services occupancy or a mercantile occupancy need not conform to Sentence (1), provided the partitions are not located in the only means of egress.
(5)Exit doors need not conform to Sentence (1) or (2), where
- (a) the doors serve accessory buildings where life safety is not adversely affected,
- (b) the doors serve storage garages or other accessory buildings serving not more than one dwelling unit, or
- (c) the doors
- (i) serve storage suites of not more than 28 m2 in gross area that are in warehousing buildings of not more than one storey, and
- (ii) open directly to the exterior at ground level.
(1)Except as permitted by Sentence (1.1) and except for doors serving single dwelling unit or a house with a secondary suite, exit doors that are required to swing shall swing in the direction of exit travel.
(1.1)An exit door need not swing in the direction of exit travel where it serves
- (a) a room, suite or floor area having an occupant load of not more than 60 persons, or
- (b) as part of a means of egress from more than one floor area and the floor areas so served have a total occupant load of not more than 60 persons..
(2)Doors that open onto a corridor or other facility that provides access to exit from a room or suite having an occupant load of more than 60 persons shall swing on the vertical axis in the direction of exit travel.
(3)Doors that divide a corridor that is not wholly contained within a suite shall swing in the direction of exit travel.
(4)Where a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall
- (a) swing in opposite directions, with the door on the right hand-side swinging in the direction of exit travel, or
- (b) swing in both directions.
(1)Except as provided in Sentence (2), the distance between a stair riser and the leading edge of a door during its swing, except for doors serving a single dwelling unit or a house with a secondary suite, shall be not less than 300 mm.
(2)Where there is a danger of blockage from ice or snow, an exit door, including doors serving a single dwelling unit, may open onto not more than one step, provided the riser of such a step does not exceed 150 mm.
(1)Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall
- (a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or
- (b) be controlled by electromagnetic locking mechanisms in accordance with Sentence 3.4.6.16.(5).
(2)Except for doors serving a single dwelling unit or a house with a secondary suite, and doors to accessory buildings and to garages serving a single dwelling unit, door release hardware on doors in a means of egress shall be operable with one hand and the door shall be openable with not more than one releasing operation.
(3)Door release hardware on doors in a means of egress shall be installed 900 mm to 1 100 mm above the finished floor.
(4)Except for hotels, a door opening onto a public corridor that provides access to exit from suites shall be designed not to lock automatically when such doors are equipped with an automatic self-closing device.
(1)Except as required by Sentence 3.8.3.3.(7), every exit door, except doors serving a single dwelling unit or a house with a secondary suite, shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90 N applied to the door release hardware.
Access to Exits
(1)An access to exit shall be provided from every roof intended for occupancy and from every podium, terrace, platform or contained open space.
(2)Where a roof is intended for an occupant load of more than 60 persons, at least 2 separate means of egress shall be provided from the roof to stairs designed in conformance with the requirements for exit stairs and located remote from each other.
(3)Where a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the appropriate requirements for rooms or suites in Article 9.9.7.4.
(1)Except as required in Sentence 9.9.9.3.(1), each suite in a floor area occupied by more than one suite shall have
- (a) an exterior exit doorway,
- (b) a doorway to a public corridor, or
- (c) a doorway to an exterior passageway.
(2)Except as provided in Sentences 9.9.7.3.(1) and 9.9.8.2.(2), from the point where a doorway described in Clause(1)(b) or (c) enters the public corridor or exterior passageway, it shall be possible to go in opposite directions to each of 2 separate exits.
(1)A dead-end public corridor is permitted in an occupancy shown in Table 9.9.7.3., where
- (a) the dead-end corridor
- (i) does not exceed the distance of travel measured from the most remote point of the dead-end to a point where it is possible to go in opposite directions to each of two separate exits, and
- (ii) is provided with doors equipped with self-closing devices, or
- (b) there is a second and separate egress doorway from each room or suite not leading into the dead-end corridor.
(2)Dead-end public corridors in residential occupancies and business and personal services occupancies shall contain only suite door openings arranged so that not more than two such doors have to be passed to reach the nearest exit.
(3)The area of wired glass in doors required by Sentence (2) shall not exceed 645 cm².
(1)Except for dwelling units, at least two egress doors shall be provided where
- (a) the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or
- (b) the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m.
(2)Doors required in Sentence (1) shall be spaced so that in the event one door is made inaccessible by a fire within such a room or suite, the other door will provide safe egress.
(1)Required access to exit from suites shall not be through any other dwelling unit, service room or other occupancy.
(1)Except for dwelling units, the travel distance from any point within the room or suite to the nearest egress door shall not exceed the maximum travel distance in Article 9.9.8.2.
Exits from Floor Areas
(1)Except as provided in Sentences (2) and (3), for the purposes of this Subsection, travel distance means the distance from any point in the floor area to an exit measured along the path of exit travel.
(2)Where a room or suite is separated from the remainder of the floor area by a fire separation having a fire-resistance rating of at least 45 min or, in a sprinklered building, by a fire separation which is not required to have a fire-resistance rating, the travel distance may be measured from an egress door of the room or suite to the nearest exit.
(3)Where a public corridor is not less than 9 m wide and conforms to Subclauses 3.4.2.5.(1)(d)(i) to (d)(iv), the travel distance may be determined in accordance with those Subclauses.
(1)Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than
- (a) 40 m in the case of business and personal services occupancies,
- (b) 45 m for all occupancies where the floor area is sprinklered, and
- (c) 30 m for all other occupancies.
(2)Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.
(3)In boarding, lodging or rooming houses,
- (a) where sleeping accommodation is provided for not more than eight persons, a single exit is permitted from each floor area, or
- (b) where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.
(1)Where more than one exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.
(1)Where more than one exit is required from a floor area, at least 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them.
(1)Not more than one exit from a floor area is permitted to lead through a lobby.
(2)The lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m.
(3)The lobby referred to in Sentence (1) shall conform in all respects to the requirements for exits, except that rooms other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly onto such lobby.
(3.1)Except as provided in Sentence (6), an exit is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space other than as described in Sentence 3.2.8.2.(6).
(4)Where the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating.
(5)Passenger elevators are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are designed to remain closed except while loading and unloading passengers.
(6)An exit that serves a hotel is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space.
(1)Except as provided by Sentences (2) and (3), the space above a mezzanine shall be served by at least two means of egress leading to exits accessible at the mezzanine level on the same basis as floor areas.
(2)One means of egress from a mezzanine is permitted, where
- (a) the mezzanine is not required to terminate at a vertical fire separation, as permitted by Sentence 9.10.12.1.(2),
- (b) the occupant load of the mezzanine is not more than 60,
- (c) the area of the mezzanine does not exceed the area limits of Clause 9.9.7.4.(1)(a), and
- (d) the distance limits of Clause 9.9.7.4.(1)(b) measured along the path of travel, are not exceeded from any point on the mezzanine to (i) an egress door serving the space that the mezzanine overlooks if the space is served by a single egress door, or (ii) an egress stairway leading to an access to exit in the space below if that space is required to be served by two or more egress doorways in conformance with Sentence 9.9.7.4.(1).
(3)One of the means of egress from a mezzanine that is not required to terminate at a fire separation as permitted by Sentence 9.10.12.1.(2) and that exceeds the limits of Sentence (2), is permitted to lead through the room in which the mezzanine is located provided all other means of egress from that mezzanine lead to exits accessible at the mezzanine level.
(4)Except as provided in Sentence (2), the maximum travel distance from any point on a mezzanine to the nearest exit shall be not more than
- (a) 40 m in a business and personal services occupancy,
- (b) 45 m in a floor area that is sprinklered throughout, provided it does not contain a high-hazard industrial occupancy, or
- (c) 30 m in any floor area not referred to in Clause (a) or (b).
Egress from Dwelling Units
(1)Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by
- (a) an egress door to a public corridor, enclosed exit stair or exterior passageway, or
- (b) an exit doorway not more than 1.5 m above adjacent ground level.
(2)Where a dwelling unit is not located above or below another suite, the travel limit from a floor level in the dwelling unit to an exit or egress door may exceed 1 storey where that floor level is served by an openable window or door
- (a) providing an unobstructed opening of not less than 1 m in height and 0.55 m in width, and
- (b) located so that the sill is not more than (i) 1 m above the floor, and (ii) 7 m above adjacent ground level.
(3)The travel limit from a floor level in a dwelling unit to an exit or egress door may exceed 1 storey where that floor level has direct access to a balcony.
(1)Except as provided in Sentence 9.9.7.3.(1) and except for dwelling units in a house with a secondary suite, where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go in opposite directions to 2 separate exits unless the dwelling unit has a second and separate means of egress.
(1)Except for dwelling units in a house with a secondary suite, a dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto
- (a) an exit stairway serving more than one suite,
- (b) a public corridor (i) serving more than one suite, and (ii) served by a single exit,
- (c) an exterior passageway (i) serving more than one suite, (ii) served by a single exit stairway or ramp, and (iii) more than 1.5 m above adjacent ground level, or
- (d) a balcony (i) serving more than one suite, (ii) served by a single exit stairway or ramp, and (iii) more than 1.5 m above adjacent ground level.
(2)Where a dwelling unit is located above another dwelling unit or common space in a house with a secondary suite, the upper dwelling unit shall be provided with as second and separate means of egress where an egress door from that dwelling unit opens onto an exterior passageway that
- (a) has a floor assembly with a fire-resistance rating less than 45 min,
- (b) is served by a single exit stairway or ramp, and
- (c) is located more than 1.5 m above adjacent ground level.
Egress from Bedrooms
(1)Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least one outside window that
- (a) is openable from the inside without the use of tools,
- (b) provides an individual, unobstructed open portion having a minimum area of 0.35 m² with no dimension less than 380 mm, and
- (c) maintains the required opening described in Clause (b) without the need for additional support.
(2)Except for basement areas, the window required in Sentence (1) shall have a maximum sill height of 1 000 mm above the floor.
(3)Where a window required in Sentence (1) opens into a window well, a clearance of not less than 550 mm shall be provided in front of the window.
(4)Where the sash of a window referred to in Sentence (3) swings towards the window well, the operation of the sash shall not reduce the clearance in a manner that would restrict escape in an emergency.
(5)Where a protective enclosure is installed over the window well referred to in Sentence (3), the enclosure shall be openable from the inside without the use of keys, tools or special knowledge of the opening mechanism.
(6)When sliding windows are used, the minimum dimension described in Sentence (1) shall apply to the openable portion of the window.
(7)Where the sleeping area within a live/work unit is on a mezzanine with no obstructions more than 1 070 mm above the floor, the window required in Sentence (1) may be provided on the main level of the live/work unit provided the mezzanine is not more than 25% of the area of the live/work unit or 20 m2, whichever is less, and an unobstructed direct path of travel is provided from the mezzanine to this window.
Signs
(1)This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite.
(1)Exits shall be located so as to be clearly visible or their locations shall be clearly indicated.
(2)Where an exit door leading directly to the outside is subject to being obstructed by a parked vehicle or storage because of its location, a visible sign prohibiting such obstructions shall be permanently mounted on the exterior side of the door.
(1)Except as required in Sentence (7), every exit door shall have an exit sign placed over it or adjacent to it if the exit serves
- (a) a building that is 3 storeys in building height,
- (b) a building having an occupant load of more than 150, or
- (c) a room or floor area that has a fire escape as part of a required means of egress.
(2)Except as required in Sentence (6), every exit sign shall
- (a) be visible on approach to the exit,
- (b) consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, "Graphical symbols – Safety colours and safety signs – Part 1: Design principles for safety signs and safety markings," and
- (c) conform to ISO 7010, "Graphical symbols – Safety colours and safety signs – Registered safety signs," for the following symbols: (i) E001 emergency exit left, (ii) E002 emergency exit right, (iii) E005 90-degree directional arrow, and (iv) E006 45-degree directional arrow.
(3)Internally illuminated exit signs shall be continuously illuminated, and
- (a) where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, "Emergency lighting equipment," or
- (b) where illumination of the sign is not powered by an electrical circuit, be (i) constructed in conformance with CAN/ULC-S572, "Standard for Photoluminescent and Self-Luminous Exit Signs and Path Marking Systems," and (ii) labelled in accordance with the time duration for which they have been tested and listed.
(4)Externally illuminated exit signs shall be continuously illuminated at all times by a light fixture supplied by an electrical circuit.
(5)The circuitry serving lighting for externally and internally illuminated exit signs shall
- (a) serve no equipment other than emergency lighting in the area where the exit signs are installed, and
- (b) be connected to an emergency power supply as described in Sentences 9.9.12.3.(2), (3) and (7).
(6)An exit sign conforming to Clauses (2)(b) and (c) with an arrow or other indicator pointing at the direction of egress shall be provided where no exit is visible from
- (a) a public corridor,
- (b) a corridor used by the public, or
- (c) a principal route serving an open floor area having an occupant load of more than 150.
(7)Except for suite doors opening directly to the exterior, every exit serving a hotel shall have an exit sign placed over it or adjacent to it.
(1)In buildings that are 3 storeys in building height, any part of an exit ramp or stairway that continues up or down past the lowest exit level shall be clearly marked to indicate that it does not lead to an exit if the portion below exit level may be mistaken as the direction of exit travel.
(1)Arabic numerals indicating the assigned floor number shall be
- (a) except in hotels, mounted permanently on the stair side of the wall at the latch side of doors to exit stair shafts,
- (b) in hotels, mounted permanently on each side of the exit doors to the exit stair shaft,
- (c) not less than 60 mm high, raised approximately 0.8 mm above the surface,
- (d) located 1 500 mm from the finished floor and not more than 300 mm from the door, and
- (e) contrasting in colour with the surface on which they are applied.
Lighting
(1)This Subsection applies to the lighting of all means of egress except those within dwelling units or a house with a secondary suite.
(1)Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.
(2)The minimum value of the illumination required by Sentence (1) shall be not less than 10 lx.
(1)Emergency lighting shall be provided in
- (a) exits,
- (b) principal routes providing access to exit in an open floor area,
- (c) corridors used by the public,
- (d) underground walkways, and
- (e) public corridors.
(2)Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.
(3)Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted.
(4)Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.
(5)The minimum value of the illumination required by Sentence (4) shall be not less than 1 1x.
(6)Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).
(7)Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, "Emergency lighting equipment."